4-DIGIT THERMOCOUPLE METERS, TRANSMITTERS & CONTROLLERS MODEL Q9000J / Q9000K / Q9000T
OPTIONS Analog output for user-selected span Single-setpoint 10 A relay control Dual-setpoint 10 A relay control Proportional 4-20 mA control Time-proportional 2 A SS relay control Parallel BCD output, isolated NEMA-4 splash-proof lens cover QUANTA Models Q9000J, Q9000K and Q9000T are 4-digit indicator/controllers for thermocouple types J, K and T, respectively. They are complete with linearization, cold-junction compensation, and sensor-break detection. Readout is in °C or °F with 0.1° resolution, as selected by push-on jumpers. What makes QUANTA exceptional is the wide choice of options. POWER OPTIONS Six types of meter power are available: 120 Vac, 240 Vac, 24 Vac, 5 Vdc, isolated 9-32 Vdc, or isolated 26-56 Vdc. ANALOG OUTPUT OPTIONS A 0.1 mV/count (±2 V full-scale) analog output is standard and is useful for driving a strip-chart recorder. An additional analog output can be provided by an optional vertical plug-in board. Available output signals are 0-5 Vdc, 0-10 Vdc, 0-1 mA (source or sink), and 4-20 mA (source or sink). The top and bottom of each output range can be scaled to fit a user-selected display span. CONTROL OUTPUT OPTIONS Additional outputs can be provided by a horizontal upper board. Available options include single-setpoint control with one 10 A relay, dual-setpoint control with two 10 A relays, 4-20 mA proportional control (source or sink), time-proportional 2 A solid-state relay control, and isolated, parallel BCD output. For additional information, please refer to the QUANTA Options, and Mechanical sections. SPECIFICATIONS ANALOG INPUT TC types: J (Iron-Constantan), K (Chromel-Alumel), T (Copper-Constantan) oo Calibration: To IPTS-68, as published in NIST monograph 125 (March 1974), ASTM E130-72 or ASA C96.2-1973 Configuration: Single-ended (-TC lead connected to ANA GND) Input resistance: 100 Mohm Sensor-break detection: 400 nA current source Max lead resistance for rated accuracy: 500ohm (type J ohm), 395ohm (type K ohm), 200ohm (type T ohm) Zero tempco (cold-junction error): ±0.06 deg/deg Span tempco, 10°C to 40°C: ±0.01% of reading/°C NOISE REJECTION NMR: 125dB at 50/60 Hz Overvoltage protection: 120 V rms (continuous), 240 V rms (30 s max) CMR: 120 dB with 250 ohm imbalance CMV: 1500 Vp per HV test, 354 Vp per IEC spacing ANALOG-TO-DIGITAL CONVERSION Input configuration: Single-ended SIG HI (TC + ) lead connected to SIG GND through 10ohm Technique: Dual-slope, average-value Polarity: Automatic Signal integration period: 100 ms Read rate: 2.5/s DISPLAY Type: 7-segment, red LED Height: 0.56 in (14.2 mm) Symbols: 8.8.8.8 Decimal point positions: Three positions selectable by jumpers behind lens or at connector 0 to 9,999 counts: Normal operation 10,000 to 19,999 counts: Four least-significant digits flash reading Beyond 19,999 counts: All four digits flash zeros Sensor-break indication: Three least-significant digits blanked POWER AC voltages: 120, 240, 100 or 24 Vac +10%/15% AC frequency: 49-63 Hz DC voltages: 9-32 Vdc, isolated to 300 Vp; 26-56 Vdc, isolated to 300 Vp; 5 V dc ±5%, non-isolated Power consumption: 5 W max ENVIRONMENTAL Operating temperature: 0 to 60°C Storage temperature: 40 to +85°C Relative humidity: 95% at 40°C (non-condensing) MECHANICAL Dimensions: Newport DIN1A (1/8 DIN) case (see Mechanical section for drawings) Weight: 17 oz (480 g) Case material: 94V-0 UL-rated polycarbonate HOME / PRODUCT GUIDE / TECHNICAL REFERENCE NEWPORT Electronics, Inc. (714) 540-4914 or Contact Us Copyright 1998, Newport Electronics, Inc. All rights reserved. |